Botswana Energy Regulatory Authority
National oversight — licences, audits, enforcement across all carriers & OMCs.

Incidents & Spills

HSSE event reporting, investigation & CAPA · 3 records

1
Critical events
1
Open / investigating
1,260 L
Product released YTD
PS-INC-26-031SpillMajorInvestigating
Foot-valve seal failure during offload; ~1,200 L released to bund and verge.
Diesel · Trans-Kalahari Carriers · A1 near Mahalapye · 2026-06-08 · 1,200 L
Root cause: Worn internal valve seal not detected at pre-despatch.
CAPA: CAPA-26-009
PS-INC-26-027NearMissCriticalClosed
ESD failed to trip on test; isolated before transfer. No release.
LPG · Mogale Fuel Logistics · Francistown Terminal gantry · 2026-06-03
Root cause: Thermal link corroded.
CAPA: CAPA-26-006
PS-INC-26-022OverfillMinorClosed
Compartment overfill at receiving; optic sensor delay. Minor surface spill.
Petrol · Kwa Nokeng Transport · Engen — Gaborone West · 2026-05-28 · 60 L
Root cause: Overfill sensor response lag.
CAPA: CAPA-26-004